When sprinklers are required in residential buildings in England, Wales and Scotland. Always confirm the requirements for your own project with your building control body.

England

Blocks of flats

Since 26 November 2020, Approved Document B has recommended sprinklers throughout new blocks of flats with a storey 11 metres or more above ground level. Before that the threshold was 30 metres. The system should be designed and installed to BS 9251 or BS EN 12845.

Care homes

Amendments to Approved Document B that came into force on 2 March 2025 say a new care home should have a sprinkler system throughout, whatever its height. Transitional arrangements apply to projects that were already under way, so check with your building control body which version applies. Sprinklers for care homes.

Houses and conversions

There is no blanket requirement for sprinklers in a new house in England. Building control often accepts, or asks for, a sprinkler system where a layout makes escape harder, such as an open-plan ground floor, a loft conversion or an extra storey. Sprinklers for your home.

Wales

Wales was the first country in the world to make sprinklers compulsory in new homes. Under the Domestic Fire Safety (Wales) Measure 2011, sprinklers have been required in new and converted care homes, hostels and similar buildings since 30 April 2014, and in all new and converted houses and flats since 1 January 2016.

Scotland

For building warrants applied for since 1 March 2021, Scotland requires fire suppression, usually sprinklers, in all new flats and maisonettes, new social housing and new shared multi-occupancy residential buildings, regardless of height.

The standard: BS 9251:2021

BS 9251 is the British Standard for sprinkler systems in residential and domestic buildings. The 2021 edition sorts buildings into four categories by risk, from single homes (Category 1) to blocks of flats over 18 metres (Category 4), and sets the design, water supply and installation requirements for each.

Safeguard is certificated by IFC Certification under SDI 22 to install residential and domestic sprinkler systems in all four categories.